General design information


Options

Download Details

Pipe design
Fitting design
Typical product dimensions
Chemical resistance information
Pressure & headloss tables
Standards & approvals


Composition

The materials used in the Equator system are listed and accepted by WBS - Water Byelaws Scheme for use in domestic installations in all the UKšs regional water authorities. The PE-X pipe system offer excellent design flexibility with temperature tolerances ranging from 120 ēC to - 20 ēC. The inherent composition of plastic pipe makes the system very light in weight, roughly one quarter that of equivalent copper pipework. Scale build up and noise from water hammer are negligible with Equator pipe.

Normal operating temperature & pressure limits for Equator pipes & fittings
Application Nominal system flow temperature ēC Max system service temperature ēC System malfunction temperature ēC System working pressure bar
Cold water system
20 20 - 12
Vented hot water systems
65 83 100 3.5
Unvented hot water systems including instantaneous heaters and/or incorporating storage (excludes discharge pipes from temperature and/or pressure relief valves)
65 95 100 6.0
Vented central heating systems
82 95 100 3.5
Sealed central heating systems (excludes discharge pipes from temperature and/or press
ure relief valves)
92 105 114 3.0
Underfloor heating
60 83 100 3.5

Note
BS 5449 states that the central heating design flow temperature shall not exceed 82 ēC. Pipe circuits prone to repeated high level over heating such as found in gravity solid fuel and solar heating systems are not suitable for Equator

Table 1

Classification

Equator is classified in accordance with BS7291 Part 3 Class S. The design life of Equator is at least 50 years when used for the applications and operating conditions listed in Table 1. Equator may also be used in hot climates and for applications such as grey water systems. For this type of application, where the cold water will become warm, without the use of a heating appliance, the maximum warm water operating limits are shown in Table 2 below.

Warm water operating temp & pressure chart
Operating water temperature, °C
Maximum pressure rating, bar
30
11.5
40
11
50
10.5