|
Equator pipe offers high performance
pressure and temperature ratings and is resistant to most
chemicals. Pipes are available in the sizes and lengths as
detailed in table 3. All outside diameters meet the requirements
as set out in BS7291: Part 3 1990: Table 1 and are therefore
consistent with metric sized copper tube.
EQUATOR PIPE MUST NOT BE USED
FOR GAS, OIL OR HIGH PRESSURE AIR SUPPLIES.
|

Table 3
|
 
Designed originally for central heating and
under floor heating systems, barrier pipe incorporates an oxygen
barrier located centrally within the pipe wall to inhibit oxygen
permeation. Barrier pipe is also suitable for hot & cold applications.

Table 4
 
The Equator system is ideal for routing
services through:
floor voids
ceiling voids
lofts
conduit piping
Where surface mounted pipework must
be used it may be preferable to use rigid pipes, ie. copper. Equator
fittings joint to copper pipe without the need for any special adaptors.
 
Equator¹s flexibility permits easy
cabling through floor joists, notching is not necessary. This method
of fixing means that pipework can be installed after the floor has
been laid, working from below. This method of installing pipework
presents several distinct advantages:
€ No risk of damage to pipework when
fixing floor boards
€ Larger pipe sizes can be routed across joist spans by drilling
compared to notching
€ There is adequate space around the pipe for correct thickness
of thermal insulation to be fitted in accordance with Building Regulations
or where required by the clients specification
The flexible nature of Equator pipework
makes it ideally suited to be cabled through proprietary timber
ŒI¹ joists, such as TJI joists used in the Silent Floor system manufactured
by TJM Europe.


|
The correct location for drilling joists is different to
the notching zone.
Holes should be drilled in accordance with BS6700, BS5449
and NHBC regulations. Figs 1 and 2 give guidance on the regulations.
To assist in calculating the 0.25 and 0.4 factors for a particular
joist span,please refer to page 10 of the Equator Design and
Installation Guide
|
|

Table 5
|
|
Fig 1

Fig 2

|
 
The use of 10mm flow and return radiator
connections is very popular with house builders as the smaller pipes
can be concealed behind plasterboard. Equator pipe is ideal for
this application and has the advantage over copper of being resilient
to impact damage which can sometimes be caused by following trades
in new builds. Several boiler manufacturers and heating designers
recommend the use of a Œhigh head¹ circulating pump whenever minibore
size pipe, pipe with diameter less than 15mm, is to be installed.
Whatever pump is specified, it is advisable to check that the circulating
head of the pump will be adequate to overcome the resistance of
10mm piping plus all other resistances of the index run. To easily
estimate the frictional loss of 10mm Equator pipework based on the
design load at 11ºC temperature drop, use Table 6 below.
Table 6



|