 |
 
Testing Techniques
Since the introduction of the new Water Regulations,
the plumbers' attention has been drawn to items such as notification
of work, pumped showers and WC flushing methods, but very little
focus on the requirement for pressure testing. Within the new Water
Regulations it is a mandatory requirement that: 'Every water system
shall be tested'. Why mandatory testing? Traditionally, the plumber
has not felt it necessary to pressure test; systems would simply
be filled with water and the joints inspected. Half a century ago
or more, this logic could perhaps be justified by the fact that
most of the pipework could be visibly inspected for leaks. Today
probably 90% of the piping joints in a typical new house are hidden
during commissioning, so visual inspection of all joints is impossible.
Yet the trend to have a cloakroom, second bathroom, etc dictates
more piping. Also the popularity of mains fed systems, means that
more assurance is desirable that the system will be safe at the
peak mains pressure, which is not achieved simply by filling during
normal working hours, when the pressure will not be at its highest.
A second reason for testing is that the drains, sanitary pipework
and gas pipework would normally be pressure tested, so why not test
the water systems also?
Water or air test? Some plumbers favour the
use of air testing kits, as filling pipework with water whilst properly
expelling the air is time consuming. However, testing with air is
not an acceptable method in accordance with the Regulations and
BS 6700: 1997. As air is compressible a leak comprising of a few
droplets will be much more visual on a pressure gauge when testing
with water. Some installers argue: ³We test both gas and sanitary
pipework using air pressure, so why not water piping?² The answer
is that both of these use a U-gauge as the measuring device, whereby
a drop of only, say 5mm can be easily be seen. Such a drop equates
to about 0.5 millibar, whereas the naked eye would struggle to detect
a drop of less than 0.1 bar (100 millibar) on a typical pressure
gauge! Therefore, the best test medium for water pressure piping
is water; that is why the Regulations and BS 6700 both require 'hydraulic
testing'. The need to pressurise Where joints are to be concealed,
simply filling-up a system with water at normal pressure is not
an adequate test. A poorly made soldered joint for example may appear
to be satisfactory at the fill pressure, and detection will only
be possible if the pressure is raised. Such a joint is often said
to be 'hanging by a hare's breath', and needs additional pressure
to expose the fault. The need for pressurisation is supported by
the many acecdotal stories of unsoldered joints held together due
to the sealing property of the flux alone. When to test The Regulations
require that 'the whole system' is tested; taken literally, many
installers may feel this to be unnecessarily onerous. In practice
it would be sensible to test the 'first fix' carcass pipework before
it is concealed. If this was done, then from a pragmatic view, is
it really necessary to then re-test the whole installation on completion
only for the sake of a few final connections, which can usually
be visually inspected during commissioning? Further, if the hot
and cold water is fed from gravity storage, then several temporary
fittings will need to be employed in the vicinity of the storage
cistern, in order to test as much of 'the whole system' as practical.
When testing such systems it will often be necessary to carry-out
two separate tests, as the hot water cylinder will not be able to
withstand the test pressure required by the mains water supply.
Direct mains water fed systems are invariably far easier to test,
as on completed installations the hot and cold water can be temporarily
linked-up in order to perform a single test. This can be achieved
by making a temporary connection to the washing machine valves using
appropriate hoses, as shown in the photograph (note also the size
of the gauge). Filling for the pressure test Hand pump test kits
are often needed in order to correctly pressurize the pipework,
but they are not efficient for filling-up the system: most pumps
will displace only about 25ml for each stroke of the pump! If a
permanent water supply is not available in the plot, try to arrange
a temporary hose connection as the method of filling the system.
Practical tips The most common mistake, which installers make when
testing, is they do not use a pressure gauge which is capable of
giving an adequate response. Gauges that are not much bigger than
a 50p coin are insufficient; the dial face should be not less than
80mm diameter. Also make sure the full-scale deflection is not excessively
more than your test pressure, for example a gauge scale that goes
up to 50 bar will not be responsive enough for your needs. Unfortunately
most commercially available hand pump test kits are not fitted with
an adequate gauge for thorough testing, and an extra test gauge
should used between the test hose and point of connection to the
system. Also you will need to detect pressure drops as small as
0.2 bar, so it would be preferable for the scale to have 0.2 bar
graduations. The second mistake is not to expel the air during filling,
as trapped air will make the gauge needle response 'spongy'. Installers
often use blank caps to form temporary plugs, which is fine for
pipework 'drops'. For upward facing 'tails' forming high points,
the use of temporary couplings, which incorporate a drain cock,
can be used to 'bleed' the air without causing excessive accidental
spillage of water. When testing the 'first fix' pipework on new
housing, the airing cupboard usually contains several upward facing
pipe tails, which can be temporarily linked in order that all the
circuits are tested in one operation. The temporary fittings employed
for testing purposes can be re-used on other plots. Equator push-fit
fittings can be re-used without the need to unscrew end caps or
reassemble joint internals with new grip rings. The Equator range
also incorporates plugs for push-fit sockets. The test method Most
uninformed installers, if questioned about a suitable duration for
a pressure test will often respond with a range of answers from
10 to 30 minutes. Such short periods are not sufficient to yield
a thorough test. The Regulations prescribe both the method and the
minimum duration for the test. The requirements vary depending on
whether the piping is metallic or plastic. The reason for this is
that plastic piping has elastomeric properties when subjected to
pressure. There are also two optional test methods for plastics;
a summary of the requirements is given in the Table below. It should
be noted that there is a discrepancy between the Regulations and
BS 6700 related to the final pressure in the plastics Test A method.
BS 6700 recommends the pressure be reduced to one half the test
value, whereas the Regulations state a value of one third. From
a practical view, the final test value used is not important; it
is more critical that the test is properly undertaken. No substitute
for quality A common misconception held by some construction supervisors
is that a 'Pass' on a pressure test record sheet signifies that
the system was correctly installed. A satisfactory test result merely
indicates that the system is currently watertight and is likely
to remain so for the foreseeable future, providing that: 1. The
test was properly undertaken. 2. The standard of workmanship for
the installation was adequate. Clearly the requirement for pressure
testing should not be seen as a reason to take a relaxed view on
the need for quality control measures, or on the importance of selecting
competent installers who fully appreciate the products they are
using. A Distance Learning booklet is freely available from Marley
to cover product awareness aspects of the Equator push-fit hot and
cold water system. The booklet can be obtained by dialling a free
phone literature hotline 0800 0281 876. It is wrong to think that
there is more need to test plastic systems than copper systems,
the Regulations require all systems to be tested. Reproduced courtesy
of Plumbing, The Institute of Plumbing's Magazine.
By Brian F Whorlow IEng FIOP RP, |
 |



Exhibition news
New Sales and Marketing
Director
Interbuild
Artisan, Craftsman,
Technician
Happy New Year!
Testing Techniques
Lord and Lady's Hall Undergoes A Princely
Transformation: October 2001
Equator Scoops Top Award
|